EasyManua.ls Logo

EMI WLHG09 - Controller Fault Conditions

EMI WLHG09
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WLCG/WLHG
High-Wall Air Handlers
Installation, Operation and Maintenance Manual
P/N 240008111, Rev. G [06/18/10] 33
Controller Fault Conditions
Unit-mounted controller fault indicationsTable 4
Code Fault condition Description
E01
Room air sensor fault If the room air sensor is disconnected, dam-
aged or malfunctions the LCD display will
ash error code E01 to signify that a fault has
occurred.
Operation will continue with the control using
the last known value for the room air sensor.
E02
Condensate fault If the control senses a condensate fault condi-
tion, either through the optional condensate
pumps safety switch or the drain pan sensors,
the LCD display will ash error code E02.
e compressor will switch o for a minimum
of three minutes and until the fault condition
is corrected.
E03
ID coil sensor fault e indoor coil sensor monitors the tempera-
ture of the indoor coil.
If a freeze condition exists continuously for
three minutes, the LCD will display error code
E03 to signify that a fault has occurred.
e compressor will switch o for a minimum
of three minutes and until the fault condition
is corrected.
If the microprocessor detects a coil freeze con-
dition four times within a 24 hour period, the
FILTER CHECK indicator will appear.