Page 102
1.5.3 Antifreeze pr.
04. 07. 2015 10:42
T ON
Glycol type
Tank
5.0°C
Water
Priority tank
1.5.4 Anti-legionellae
04. 07. 2015 10:43
Repetition
T legionellae
t-ON
t-monitor
Activation
1 day
60.0°C
01:00
60min
1.5.5 Cooling funct.
04. 07. 2015 10:43
Activation
Hyst.tank 1
Hyst.tank 2
t-ON
t OFF
2.0K
2.0K
00:00
07:00
PROFESSIONAL MODE
Here, the parameters for tank cooling are
dened.
›t-ON‹ and ›t-OFF‹ are used to dene the
appropriate time slot in which the tank is to
be cooled via the collector, and ›Hyst.tank
1‹ and ›Hyst.tank 2‹ are used to dene the
switch-ON hysteresis.
Continue to scroll.
These parameters must be set by the tter
based on the applicable national regulations.
›Function‹ is used to dene the period in
days (1day - 7days) during which legionella
reduction must have occurred at least once.
›t-ON‹ is used to dene the time of a
possibly required reheating cycle.
›T legionellae‹ denes the disinfection
temperature. ›t monitor‹‹ is used to
dene the minimum disinfection time.
Continue with ›Tank cooling‹.
In the case of plants with two tanks,
the source of the anti-freeze protection
heat must be selected by specifying
›Priority tank‹ or ›Secondary tank‹.
Continue with ›Anti-legionellae‹.