Test outputs
Holiday function
Next
0.7 Checklist
04. 07. 2015 09:26
0.8 Parameter
04. 07. 2015 09:27
T limit 1
T max.tank 1
T limit 2
T max.tank 2
If T-limit>60°, anti-scalding
60.0°C
59.0°C
60.0°C
59.0°C
0.8 Parameter
04. 07. 2015 09:27
protection must be installed.
Antifreeze protect.
Tube collector
Post Heating Requ.
Next
Selecting „antifreeze protection“.
COMMISSIONING MODE
„0.8 Parameter“ appears
Setting the limit temperatures:
The tanks are only loaded until the maximum
temperature „T max. tank“ has been reached.
In case of imminent collector overheating, the
tanks are loaded to „T limit“.
If the temperature in a tank exceeds the „T
limit“ value, the solar circuit pump is im-
mediately turned off and not turned on until
the temperature has fallen below the „T limit“
value.
Complete the checklist by pressing „Next“.