1.3.2 Tube collector
04. 07. 2015 09:28
Activation
Start
t-ON
T ON
t solar 1
time-dependent
10min
20.0°C
20s
1.3.2 Tube collector
04. 07. 2015 09:28
n solar 1
t solar 2
n solar 2
t start
t end
100%
0s
30%
06:00
20:00
0.8 Parameter
04. 07. 2015 09:29
protection must be installed.
Antifreeze protect.
Tube collector
Post Heating Requ.
Next
If a hydraulic scheme including boiler control
functions has been selected, the post heating
requirements are congured here.
Select „Post heating req.“.
COMMISSIONING MODE
... the pump delivery rate as a
percentage value can be entered.
The two time programs are
performed one after the other.
Continue via the menu item
›Holiday function‹.
Press ›esc‹ to return.
To receive correct measured values from
the tube collector system, the pump
must be switched ON briey.
By activation of the function, the
solar circuit pump can be started
time- and/or temperature-controlled.
The time sequence, the pump ON time and ...