Page 88
1.2.6 Min.temperat...
04. 07. 2015 10:34
Activation
T min.Coll 1
Hyst.Coll. 1
20.0°C
2.0K
1.2.8 Priority charg...
04. 07. 2015 10:34
Priority
t pause
t charge
dT Coll.
Tank 1
2min
20min
2.0K
1.3 Basic functions
04. 07. 2015 10:35
Thermostat
Output parameter
Tube collector
Holiday function
Collector cooling
PROFESSIONAL MODE
To increase efciency on charging
the tanks, the minimum temperature
to be present at the collector in
question is entered via ›T min. Coll‹.
The relevant hysteresis value represents
the difference between the switch-ON
and switch-OFF temperature.
Continue via the menu item ›Priority charge‹.
In case of dual-tank systems, the tank
to be charged rst is dened: tank 1,
tank 2 or parallel charging.
In case of multi-zone tanks, the charging
zone which is charged rst is specied: Top
tank / bottom tank / without break
›t pause‹ is used to set the pause
time between twot switch-ON tests.
›t charge‹ serves to dene the
charging time for the secondary tank.
Once ›dT Coll‹ is reached,
the pause time is restarted.
Continue with ›Basic functions‹.
The following items appear under ›1.3. Basic
functions‹ next to the operation mode menus:
- ›Thermostat‹
- ›Output parameter‹
- ›Collector cooling‹
- ›Post Heating Requ. ...