1.2 Settings
04. 07. 2015 10:33
Max.temp.shutoff
Min. temperature
Priority charging
Buzzer
Factory settings
1.2.3 Temp.limitation
04. 07. 2015 10:34
Hyst
T limit 1
T limit 2
If T-limit>60°, anti-scalding
protection must be installed.
5.0K
60.0°C
60.0°C
1.2.5 Max.temp.sh...
04. 07. 2015 10:34
T max.tank 1
T max.tank 2
59.0°C
59.0°C
PROFESSIONAL MODE
After scrolling:
- ›Min. temperature‹
- ›Priority charging‹
Call up menu item ›Temp. limitation‹.
If the temperature in tank 1 exceeds the
value T limit 1, or if the temperature in
tank 2 exceeds the value T limit 2, the solar
circuit pump is switched off unconditionally.
The pump is not switched on again
until the actual temperature falls below
the value T limit by the hysteresis ›Hyst‹.
Example: T limit =60°C minus Hyst=5K
=> Reclosing temperature 55°C.
Continue via the menu
item ›Max.temp.shutoff‹.
Maximum temperature of the
tanks 1 and 2, to avoid excessively
hot water in the tank; the tank in
question is only charged to its ›T max‹.
In case of collector overheating,
the tank can be charged up to ›T-limit‹.
Continue via the menu item
›Min. temperature‹.