Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Appendix
Endress+Hauser 127
Expert È Application È Totalizer 2 (Deltabar M)
!
Note!
With the "Flow in %" flow type setting, the totalizer is not avaialble and is not displayed at this
position.
10.2.6 Diagnosis
Expert È Diagnosis
Parameter name Description
Eng. unit totalizer 2
(065) (066) (067) (068)
Selection
Select the unit for totalizer 2.
See also "Eng. unit totalizer 1".
The Direct Access Code depends on the selection in the "Flow meas. type" (044)
parameter:
– (065): Flow. meas. type "Mass"
– (066): Flow. meas. type "Gas norm. cond."
– (067): Flow. meas. type "Gas. std. cond."
– (068): Flow. meas. type "Volume process cond."
Factory setting:
m
3
Totalizer 2 mode (177) Define the behavior of the totalizer.
Options:
• Balanced: Integration of all measured flows (positive and negative)
• Pos. flow only: only positive flows are integrated.
• Neg. flow only: only negative flows are integrated.
• Hold: No flow is integrated. The totalizer keeps its current value.
Factory setting:
Pos. flow only
Totalizer 2 failsafe (178) Define the behavior of the totalizer in the case of an error.
Options:
• Run: Totalizing is continued.
• Hold: The totalizer is stopped and keeps its current value.
Totalizer 2 (069)
Display
Displays the total flow value of totalizer 2. The "Totalizer 2overflow" (070) parameter
displays the overflow.
See the example for "Totalizer 1"
Totalizer 2 overflow (070)
Display
Displays the overflow value of totalizer 2.
See the example for "Totalizer 1".
Parameter name Description
Diagnostic code (071)
Display
Displays the diagnostic message with the highest priority currently present.
Last diag. code (072)
Display
Displays the last diagnostic message that occurred and was rectified.
!
Note!
• Digital communication: the last message is displayed.
• The messages listed in the "Last diag. code" parameter can be deleted via the "Reset
logbook" parameter.
Reset logbook (159)
Selection
With this parameter, you reset all the messages of the "Last diag. code" parameter and the
"Last diag. 1" to "Last diag. 10" event log.
Options:
• Abort
•Confirm
Factory setting:
Abort
Min. meas. press. (073)
Display
Displays the lowest pressure value measured (peakhold indicator). You can reset this
indicator by means of the "Reset peakhold" parameter.
Max. meas. press. (074)
Display
Displays the highest pressure value measured (peakhold indicator). You can reset this
indicator by means of the "Reset peakhold" parameter.