Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Commissioning
Endress+Hauser 65
!
Note!
The measured variables %, level, volume and mass are available for this level mode ä 114
"Output unit (025)".
7 Enter the volume value for the lower calibration point
via the "Empty calib." parameter, here 0 liters for
example.
Menu path: Setup Extended setup Level Empty
calib.
P01-xxxxxxxx-05-xx-xx-xx-029
P01-xxxxxxxx-05-xx-xx-xx-032
P01-xxxxxxxx-05-xx-xx-xx-033
Fig. 34: Calibration with reference pressure –
wet calibration
1 See Table, Step 11.
2 See Table, Step 7.
3 See Table, Step 8.
4 See Table, Step 9.
5 See Table, Step 10.
6 See Table, Step 12.
7 See Table, Step 13.
8 Enter the height value for the lower calibration point via
the "Empty height" parameter, here 0.5 m (1.6 ft) for
example.
Menu path: Setup Extended setup Level Empty
height
9 Enter the volume value for the upper calibration point
via the "Full calib." parameter, here 1000 liters (264 US
gal) for example.
Menu path: Setup Extended setup Level Full
calib.
10 Enter the height value for the upper calibration point via
the "Full height" parameter, here 4.5 m (15 ft) for
example.
Menu path: Setup Extended setup Level Full
height
11 Enter the density of the medium via the "Adjust density"
parameter, here "1 g/cm
3
" (1 SGU) for example.
Menu path: Setup Extended setup Level Adjust
density
12 Set the volume value for the lower current value (4 mA)
via the "Set LRV" parameter.
Menu path: Setup Extended setup Current output
Set LRV
13 Set the volume value for the upper current value
(20 mA) via the "Set URV" parameter.
Menu path: Setup Extended setup Current output
Set URV
14 If the process uses a medium other than that on which
the calibration was based, the new density has to be
specified in the "Process density" parameter.
Menu path: Setup Extended setup Level
Process density
15 Result:
The measuring range is set for 0 to 1000 l (264 US gal).
Description
4.58
0.5
h
[m]
50 450
p
[mbar]
h =
p
r · g
r = 1
g
cm
3
➀
1000
0
V
[l]
0.5 4.5
➁
➂
h =
p
ρ · g
h
[m]
➃
➄