Deltapilot S FOUNDATION Fieldbus Commissioning
Endress+Hauser 27
The measured
variable is not in
direct proportion to
the measured
pressure as is the
case with tanks
with a conical
outlet, for example.
A linearization
table has to be
entered for the
calibration.
LEVEL
SELECTION: level
standard/
LEVEL MODE:
pressure linearized
Via the LINd.
MEASURAND
parameter:
Pressure + %
Pressure +
volume
Pressure + mass
Calibration with
reference
pressure:
semiautomatic
entry of
linearization
table, see
Operating
Instructions
BA00303P.
Calibration
without
reference
pressure:
manual entry of
linearization
table, see
Operating
Instructions
BA00303P.
Incorrect entries
are denied by
the device
Customer-specific
units of level,
volume and
mass are
possible
The measured
value display and
the TANK
CONTENT
parameter display
the measured
value.
–Two measured
variables are
required or
the tank shape is
given with value
pairs, e.g. height
and volume.
The 1st measured
variable % height or
height must be in
direct proportion to
the measured
pressure. The 2nd
measured variable
volume, mass or %
must not be in
direct proportion to
the measured
pressure. A
linearization table
has to be entered
for the 2nd
measured variable.
The 2nd measured
variable is assigned
to the 1st measured
variable by means
of this table.
LEVEL
SELECTION: Level
standard/
LEVEL MODE:
Height linearized
Via the COMB.
MEASURAND
parameter:
Height +
volume
Height + mass
Height + %
%-height +
volume
%-height + mass
%-height + %
Calibration with
reference
pressure: wet
calibration and
semiautomatic
entry of
linearization
table, see
Operating
Instructions
BA00303P.
Calibration
without
reference
pressure: dry
calibration and
manual entry of
linearization
table, see
Operating
Instructions
BA00303P.
Incorrect entries
are denied by
the device
Customer-specific
units of level,
volume and
m
ass are
possible
The measured
value display and
the TANK
CONTENT
parameter display
the 2nd measured
value (volume,
mass or %).
The LEVEL
BEFORE LIN
parameter displays
the 1st measured
value
(%-height or
height).
Measuring task LEVEL
SELECTION/
LEVEL MODE
Measured
variable selection
Description Comment Measured value
display