Commissioning Deltapilot S FOUNDATION Fieldbus
28 Endress+Hauser
5.4.3 Quick Setup menu for the Level measuring mode
!
Note!
• Some parameters are only displayed if other parameters are appropriately configured. For
example, the EMPTY CALIBRATION parameter is only displayed in the following instances:
– LEVEL SELECTION "Level easy pressure" and CALIBRATION MODE "Wet"
– LEVEL SELECTION "Level standard", LEVEL MODE "Linear" and CALIBRATION MODE
"Wet"
The LEVEL MODE and CALIBRATION MODE parameters are in the BASIC SETUP function
group.
• The following parameters are set to the following values at the factory:
– LEVEL SELECTION: Level easy pressure
– CALIBRATION MODE: Wet
– OUTPUT UNIT or LIN. MEASURAND: %
– EMPTY CALIBRATION: 0.0
– FULL CALIBRATION: 100.0
• The Quick Setup is suitable for easy and quick commissioning. If you want to make more
complex settings like changing the unit from "%" to "m", the calibration must be performed
via the BASIC SETUP group. → See Operating Instructions BA00303P.
P01-FMB70xxx-19-xx-xx-en-015
Fig. 7: Quick Setup menu for the "Level" measuring mode"
1) 1)2)1)
1)
1)
3)
3)
EMPTY CALIB.
FULL CALIB.
LEVEL SELECTION
1) On-site display only
2) FieldCare only
3) – LEVEL SELECTION "Level Easy Pressure"
and CALIBRATION MODE "Wet"
– LEVEL SELECTION = "Level Standard",
LEVEL MODE = "Linear" and
CALIBRATION MODE = "Wet"
POS. ZERO ADJUST
DAMPING VALUE
MEASURED VALUE
QUICK SETUP
GROUP SELECTION
MEASURING MODEMEASURING MODELANGUAGE
Pressure Level
OPERATING MENU