Deltapilot S FOUNDATION Fieldbus Commissioning
Endress+Hauser 29
!
Note!
For local operation see also → ä 14, Section 4.2.3 "Function of the operating elements – onsite
display connected" and → ä 15, Section 4.3 "Onsite operation via onsite display".
Local operation FieldCare
Measured value display
Switch from the measured value display to the GROUP
SELECTION with F.
Measured value display
Select QUICK SETUP menu.
GROUP SELECTION
Select the MEASURING MODE.
Measuring Mode
Select the Primary Value Type parameter.
MEASURING MODE
Select "Level".
Primary Value Type
Select "Level" option.
LEVEL SELECTION
Select the level mode. For an overview, see → ä 26.
LEVEL SELECTION
/ Level Selection
Select the level mode. For an overview, see → ä 26.
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the
measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option,
i.e. you assign the value 0.0 to the pressure present.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the
measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option,
i.e. you assign the value 0.0 to the pressure present.
EMPTY CALIBRATION
1)
Enter level value for the lower calibration point.
For this parameter, enter a level value which is assigned to
the pressure present at the device.
EMPTY CALIBRATION
1
Enter level value for the lower calibration point.
For this parameter, enter a level value which is assigned to
the pressure present at the device.
FULL CALIBRATION
1
Enter level value for the upper calibration point.
For this parameter, enter a level value which is assigned to
the pressure present at the device.
FULL CALIBRATION
1
Enter level value for the upper calibration point.
For this parameter, enter a level value which is assigned to
the pressure present at the device.
DAMPING VALUE
Enter damping time (time constant τ). The damping affects
the speed at which all subsequent elements, such as the
onsite display, measured value and OUT Value of the Analog
Input Block react to a change in the pressure.
DAMPING VALUE
Enter damping time (time constant τ). The damping affects
the speed at which all subsequent elements, such as the
onsite display, measured value and OUT Value of the Analog
Input Block react to a change in the pressure.
1) – LEVEL SELECTION "Level easy pressure" and CALIBRATION MODE "Wet"
– LEVEL SELECTION "Level standard", LEVEL MODE "Linear" and CALIBRATION MODE "Wet"