Level measurement (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
24 Endress+Hauser
11 By means of the Scale Out/SCALE OUT "EU at 0%"
parameter, enter a level value, here 0m for example.
P01-xxxxxxxx-05-xx-xx-xx-011
1 See Table, Step 11.
2 See Table, Step 13.
12 Fill the container up to the upper level point.
The related pressure value can be viewed via the
Pressure/PRESSURE parameter.
13 By means of the Scale Out/SCALE OUT "EU at 100%"
parameter, enter a level value, here 3m for example.
14 Set the Pressure Transducer Block to the "Auto" block
mode.
15 Where necessary, configure the Channel/CHANNEL
( ä 96), Linearization Type/L_TYPE ( ä 97),
Transducer Scale/XD_SCALE ( ä 95) and Output
Scale/OUT_SCALE ( ä 96) parameters by means of
the Analog Input Block.
Description
3
0
h
[m]
0 300
p
[mbar]