Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 39
Display Transducer Block
This Block does not return any output variables. It contains all the parameters for configuring
the local operation such as Language/DISPLAY_LANGUAGE and Display Contrast/
DISPLAY_CONTRAST.
Function blocks
Deltabar S: 3 Analog Input Blocks (AI), Cerabar S and Deltapilot S: 2 Analog Input Blocks (AI)
Discrete Output Block (DO)
PID Block (PID)
Arithmetic Block (ARB)
Signal Characterizer Block (SCB)
Input Selector Block (ISB)
Analog Alarm Block (AALB)
Integrator Block (IT)
Discrete Input Block (DI)
!
Note!
Endress+Hauser Guideline BA00062S.
The guideline provides an overview of the standard function blocks that are described in
FOUNDATION Fieldbus Specifications FF 890 - 894.
It is designed to help operators use the blocks implemented in the Endress+Hauser field devices.
Block configuration when device is delivered
The block model shown below illustrates the block configuration when the device is delivered.
P01-xMx7xxxx-02-xx-xx-en-000
Fig. 16: Block configuration when delivered
Cerabar S/Deltapilot S
The Pressure Transducer Block returns the Primary Value (pressure measured value) and the
Secondary Value (sensor temperature). The Primary Value and Secondary Value are each
transmitted to an Analog Input Block via the Channel/CHANNEL parameter ( ä 96,
Channel/CHANNEL parameter description). The Discrete Output, Discrete Input, PID, Arithmetic,
Signal Characterizer, Input Selector, Integrator and Analog Alarm Block are not connected in the
as-delivered configuration. (IT, DI)
Pressure
Transducer Block
Analog Input Block 1
CHANNEL = 1
L_TYPE = Direct
Analog Input Block 2
CHANNEL = 2
L_TYPE = Direct
Analog Input Block 3
CHANNEL = 6
L_TYPE = Direct
DP Flow
Transducer Block
Diagnostic
Transducer Block
Service
Transducer Block
Primaryvalue
Secondaryvalue
Resource Block
Integrator
Block
Discrete Input
Block
PIDBlock
Analog Alarm
Block
Input Selector
Block
Signal
Characterizer
Block
Discrete Output
Block
ArithmeticBlock
Display
Transducer Block
Deltabar only
Measured variable
Sensor
Signal evaluation
Display
withscaling
TOTALIZER 1