Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
40 Endress+Hauser
Deltabar S
The Pressure Transducer Block returns the Primary Value (pressure measured value) and the
Secondary Value (sensor temperature). In the DP Flow Transducer Block, the flow is totalized in the
"Flow" measuring mode and output by means of the Totalizer 1/TOTALIZER_1_VALUE parameter.
The Primary Value, Secondary Value and Totalizer1/TOTALIZER_1_VALUE are each transmitted
to one Analog Input Block via the Channel/CHANNEL parameter (→ ä 96, Channel/CHANNEL
parameter description). The Discrete Output, PID, Arithmetic, Signal Characterizer, Input Selector
and Analog Alarm Block are not connected in the as-delivered state. (IT, DI)
!
Note!
Please note that the links between the blocks are deleted and the FF parameters are reset to the
default values following a reset by means of the Restart/RESTART parameter in the Resource Block,
"Default" option.