Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 45
Confirm Time/
CONFIRM_TIME
Entry
Index: 33
Data type: Unsigned32
Access: auto, OOS
Enter the confirmation time for the event report. If the device does not receive confirmation
within this time, the event report is sent to the fieldbus host system again.
Factory setting:
640000
1
/
32
ms
Write Lock/
WRITE_LOCK
Display
Index: 34
Data type: unsigned8
Access: read only
Displays the status of DIP switch 1 on the electronic insert.
You can lock or unlock parameters relevant to the measured value with DIP switch 1.
If operation is locked by means of the Insert Pin No/SW_LOCK parameter ( ä 47),
you can only unlock operation again by means of this parameter.
See also Operating Instructions BA00301P (Deltabar S) or BA00302P (Cerabar S) or
BA00372P (Deltapilot S), "Locking/unlocking operation" section.
Possibilities:
Locked: Security locking switched on, i.e. the parameters cannot be written to.
Not locked: Security locking switched off. Depending on the block mode in question, it is
possible to write to the parameters (see Tables, "Parameter" column, access).
Factory setting:
Locked (locking switched on)
Update Event/
UPDATE_EVT
Display
Index: 35
Data type: DS-73
Access: read only
The Update Event/UPDATE_EVT parameter is a structured parameter consisting of five
elements.
UNACKNOWLEDGED
This element is set to "Unacknowledged" as soon as a static parameter changes.
UPDATE_STATE
Indicates whether the change was reported.
TIME_STAMP
Displays the date and time when a static parameter was changed.
STATIC_REVISION
The revision counter is increased each time a static parameter is changed.
RELATIVE_INDEX
Displays the altered parameter in the form of the relative index. See also this Table,
"Parameter, Index" column.
Block Alarm/
BLOCK_ALM
Display, selection
Index: 36
Data type: DS-72
Access: auto, OOS
The Block Alarm/BLOCK_ALM parameter is a structured parameter consisting of five
elements.
UNACKNOWLEDGED
If the "Deactivated" option was selected for the alarm that occurred by means of the
Acknowledge Option/ACK_OPTION parameter, this alarm can only be acknowledged by
means of this element.
ALARM_STATE
Use this function to display the current block condition with information on pending
configuration, hardware or system errors. The following block alarm messages are possible
with the Resource Block:
Simulate active
–Out of service
TIME_STAMP
Displays the time when the alarm occurred.
SUB_CODE
Displays the reason why the alarm was reported.
VALUE
Displays the value of the corresponding parameter at the time the alarm was reported.
Resource Block
Parameter Description