Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 79
Reset Peakhold/
RESET_PEAK_HOLD
Selection
Index: 37
Data type: unsigned8
Access: auto, OOS
This parameter lists all the peak hold indicator parameters that can be reset. You can select
the peak hold indicators you want to reset.
Options:
•None
•Max. pressure
•Min. pressure
•Pmax history
• Pmin history
•Max. temp.
•Min. temp.
•Tmax history
• Tmin history
•Reset all
Factory setting:
None
Pressure/PRESSURE
Display
Index: 38
Data type: DS-65
Access: read only
The Pressure/PRESSURE parameter is a structured parameter consisting of two elements.
VALUE
• Displays the measured pressure after sensor recalibration, position adjustment and
damping. This value corresponds to the Primary Value/PRIMARY_VALUE parameter in
the "Pressure" measuring mode.
STATUS
• Displays the status.
P01-xMD7xxxx-05-xx-xx-en-011
!
Note!
You can transmit the value and status of this parameter via the Channel/CHANNEL
parameter (→ ä 96) in the Analog Input Block. The Channel/CHANNEL must be set to "3"
for this purpose.
Corrected Press./
CORRECTED_PRESSURE
Display
Index: 39
Data type: float
Access: read only
Displays the measured pressure after sensor trim and position adjustment and before
damping.
→ See also the graphic for Pressure/PRESSURE.
Meas. Val. Trend/
MEASURED_VALUE_
TREND
Display
Index: 40
Data type: unsigned8
Access: read only
Displays the trend of the pressure measured value.
Possibilities: increasing, decreasing, constant
Max. Turndown/
MAX_TURNDOWN
Display
Index: 41
Data type: float
Access: read only
Displays the maximum possible turndown of the transmitter.
Service Transducer Block
Parameter Description
P
PV
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim
Transducer Block
PRESSURE_1_
AFTER_DAMPING/
PRESSURE
PRESSURE_1_
AFTER_CALIBRATION/
CORRECTED PRESS.
PRESSURE_1_
AFTER_SENSOR/
SENSOR PRESSURE