Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
86 Endress+Hauser
Totalizer 1/
TOTALIZER_1_VALUE
Display
Index: 25
Data type: DS-65
Access: read only
The Totalizer 1/TOTALIZER_1_VALUE parameter is a structured parameter consisting of
two elements.
VALUE
Displays the total flow value of totalizer 1. You can reset the value with the Reset Totalizer
1/TOTALIZER_1_RESET parameter.
STATUS
Displays the status.
!
Note!
You can transmit the value and status of this parameter via the Channel/CHANNEL
parameter ( ä 96) in the Analog Input Block. The Channel/CHANNEL must be set to
"6" for this purpose.
You can transmit the value and status of this parameter via the Channel/CHANNEL
parameter in the Discrete Output Block. The Channel/CHANNEL must be set to "2" for
this purpose.
Totalizer 1 Unit/
TOTALIZER_1_UNIT
Selection
Index: 26
Data type: unsigned16
Access: read, write, OOS
Select the unit for totalizer 1.
Depending on the setting in the Flow-Meas. Type/FLOW_MEAS_TYPE parameter
( ä 82) this parameter offers a list of volume, norm volume, standard volume and mass
units. When a new volume or mass unit is selected, totalizer-specific parameters are
converted and displayed with the new unit within a unit group. When the flow mode is
changed, the totalizer value is not converted.
Factory setting:
m
3
Neg. Flow Tot. 1/
TOTALIZER_1_MODE
Selection
Index: 27
Data type: unsigned8
Access: read, write, OOS
Specify the way of counting negative flows for totalizer 1.
P01-xMD7xxxx-16-xx-xx-en-003
Factory setting:
Positive
Fail Safe Mode/
TOTALIZER_1_FAIL_
SAFE_MODE
Selection
Index: 28
Data type: unsigned8
Access: read, write
Select the mode for totalizer 1 in the event of an error.
Currently, only the "Actual" mode can be selected, i.e. totalizer 1 continues to count in the
event of an error.
Reset Totalizer 1/
TOTALIZER_1_RESET
Selection
Index: 29
Data type: unsigned8
Access: read, write, OOS
You reset totalizer 1 to zero with this parameter.
Options:
Abort (do not reset)
•Reset
Factory setting:
Abort
DP Flow Transducer Block
Parameter Description
Options
Stop on neg. flow
Dec. on neg. flow
Inc. on. neg. flow
negative flow
Total remains constant
Total decreases
Total increases
Total increases
Total increases
Total increases
positive flow