Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 87
Tot. 1 User Unit/
CUSTOMER_UNIT_
TOT_1
Entry
Index: 30
Data type: visible string
Access: read, write
Enter text (unit) for customer-specific unit for totalizer 1.
You can enter a maximum of eight alphanumeric characters here.
→ See also Fact. U. U. Total.1/CUSTOMER_UNIT_FACTOR_TOT_1.
Prerequisite:
• Totalizer 1 Unit/TOTALIZER_1_UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the customer-
specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation. The
maximum number of characters in the counter is again limited to five. For example if the
customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed. In the FF
configuration program, the slash counts as a character, i.e. "crates/m2" would be displayed as
"crates/m".
Factory setting:
_ _ _ _ _ _ _ _
Fact. U. U. Total.1/
CUSTOMER_UNIT_FAC
TOR_TOT_1
Entry
Index: 31
Data type: float
Access: read, write
Enter the conversion factor for a customer-specific unit for totalizer 1.
The conversion factor must be entered in relation to an appropriate SI unit, e.g. m
3
for the
"Volume operat. cond." Flow-Meas. Type/FLOW_MEAS_TYPE.
→ See also Tot. 1 User Unit/CUSTOMER_UNIT_TOT_1.
Prerequisite:
• Totalizer 1 Unit/TOTALIZER_1_UNIT = User unit
Example: You want the measured value to be displayed in "buckets".
– Primary Value/PRIMARY_VALUE =1 m3 i 100 bucket
– Enter Tot. 1 User Unit/CUSTOMER_UNIT_TOT_: bucket
– Enter Fact. U. U. Total.1/CUSTOMER_UNIT_FACTOR_TOT_1: 100
– Result: Primary Value/PRIMARY_VALUE = 100 bucket
Factory setting:
1.0
Totalizer 2/
TOTALIZER_2_VALUE
Display
Index: 32
Data type: float
Access: read only
Displays the total flow value of totalizer 2. You cannot reset totalizer 2.
Prerequisite:
• Deltabar S differential pressure transmitter
Total. 2 Eng. Unit/
TOTALIZER_2_UNIT
Selection
Index: 33
Data type: unsigned16
Access: read, write
Select the unit for totalizer 2.
→ ä 87, Totalizer Transducer Block, parameter description for Tot. 1 User Unit/
CUSTOMER_UNIT_TOT_1.
Prerequisite:
• Deltabar S differential pressure transmitter
Factory setting:
m³
Neg. Flow Tot. 2/
TOTALIZER_2_MODE
Entry
Index: 34
Data type: UNSIGNED8
Access: read, write, OOS
Specify the way of counting negative flows for totalizer 2.
→ ä 86, Totalizer Transducer Block, parameter description for Neg. Flow Tot. 1/
TOTALIZER_1_MODE
Prerequisite:
• Deltabar S differential pressure transmitter
Tot. 2 Unit Text/
CUSTOMER_UNIT_
TOT_2
Selection
Index: 35
Data type: visible string
Access: read, write
Enter text (unit) for customer-specific unit for totalizer 2.
→ ä 87, Totalizer Transducer Block, parameter description for Tot. 1 User Unit/
CUSTOMER_UNIT_TOT_1.
Prerequisite:
• Deltabar S differential pressure transmitter
• Total. 2 Eng. Unit/TOTALIZER_2_UNIT = User unit
Factory setting:
- - - - - - - - - - -
DP Flow Transducer Block
Parameter Description