Flowmeter Proline 200 Electrical connection
Endress+Hauser 15
5.1.4 Terminal assignment
Transmitter
Connection version for FOUNDATION Fieldbus, pulse/frequency/switch output
+
1
2
4
+
3
1
2
3
A0013570
+
1
2
4
+
3
1
2
3
A0018161
Maximum number of terminals Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
1
2
3
Output 1: FOUNDATION Fieldbus
Output 2 (passive: pulse/frequency/switch output
Ground terminal for cable shield
Order code for "Output" Terminal numbers
Output 1 Output 2
1 (+) 2 (-) 3 (+) 4 (-)
Option E
1) 2)
FOUNDATION Fieldbus
Pulse/frequency/switch output
(passive)
1) Output 1 must always be used; output 2 is optional.
2) FOUNDATION Fieldbus with integrated reverse polarity protection.
5.1.5 Pin assignment of device plug
1
2
4
3
Pin Assignment Coding Plug/socket
1 + Signal + A Plug
2 - Signal –
3 Grounding
4 Not assigned
5.1.6 Shielding and grounding
Optimal electromagnetic compatibility (EMC) of the fieldbus system can be guaranteed only if
the system components and, in particular, the lines are shielded and the shield forms as
complete a cover as possible. A shield coverage of 90 %is ideal.
1. To ensure optimal EMC protection, connect the shield to the reference ground as often
as possible.