TMT162 Technical data
Endress+Hauser 43
10.0.2 Output
Output signal Analog 4 to 20 mA, 20 to 4 mA
Signal on alarm Breakdown information to NAMUR NE 43
Breakdown information is created when the measuring information is invalid or not present
anymore and gives a complete listing of all errors occuring in the measuring system.
The high alarm is adjustable between 21.6 mA and 23 mA allowing for flexibility when working
with the requirements of most control systems.
Load Max. (V
power supply
- 11 V) / 0.022 A (current output)
Linearization/
transmission behavior
Temperature linear, resistance linear, voltage linear
Thermocouples (TC)
to NIST Monograph 175,
IEC 60584
to ASTM E988
to DIN 43710
Type B (PtRh30-PtRh6)
1)
2)
Type E (NiCr-CuNi)
Type J (Fe-CuNi)
Type K (NiCr-Ni)
Type N (NiCrSi-NiSi)
Type R (PtRh13-Pt)
Type S (PtRh10-Pt)
Type T (Cu-CuNi)
Type C (W5Re-W26Re)
Type D (W3Re-W25Re)
Type L (Fe-CuNi)
Type U (Cu-CuNi)
32 to 3308 °F (0 to +1820 °C)
-454 to 1832 °F (-270 to +1000 °C)
-346 to 2192 °F (-210 to +1200 °C)
-454 to 2501 °F (-270 to +1372 °C)
-454 to 2372 °F (-270 to +1300 °C)
-58 to 3214 °F (-50 to +1768 °C)
-58 to 3214 °F (-50 to +1768 °C)
-454 to 752 °F (-270 to +400 °C)
32 to 4208 °F (0 to +2320 °C)
32 to 4523 °F (0 to +2495 °C)
-328 to 1652 °F (-200 to +900 °C)
-328 to 1112 °F (-200 to +600 °C)
900 °F (500 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
90 °F (50 °C)
900 °F (500 °C)
900 °F (500 °C)
90 °F (50 °C)
900 °F (500 °C)
900 °F (500 °C)
90 °F (50 °C)
90 °F (50 °C)
Internal cold junction (Pt100)
Accuracy of cold junction: ± 1.8 °F (± 1 °C)
Max. sensor resistance 10 kΩ (if sensor resistance is greater than 10 kΩ, error message as per NAMUR NE 89)
3)
Voltage transmitter (mV) Millivolt transmitter (mV) -20 to 100 mV 5 mV
1) High measuring error increase for temperature lower than 572 °F (300 °C).
2) When operating conditions are based over a large temperature range, the TMT162 offers you the ability to do a split range. For example a Type S or R thermo-
couple can be used for the low range and a Type B can be used for the upper range. The TMT162 is then programmed by the end user to switch at a prede-
termined temperature. This allows for utilization of the best performance from each individual thermocouple and provides 1 output that represents the process
temperature. Note the dual sensor option must be requested when placing an order.
3) Basic requirements NE 89:
Detection of increased wire resistance (e.g. corrosion of contacts or wires) of TC or RTD/4-wire. Warning - exceeding ambient temperature.
Input Designation Measuring range limits Min. span
Signal (mA)
Under ranging Standard 3.8
Over ranging Standard 20.5
Sensor break; sensor short circuit low To NAMUR NE 43 3.6
Sensor break; sensor short circuit high To NAMUR NE 43 21

Other manuals for Endress+Hauser iTEMP HART TMT162