TMT182 6 Commissioning
Endress+Hauser 19
Commuwin II operating matrix
ƒig. 12: : Commuwin II operating matrix:
A = Unit functions only active on customer specific linearization
B = Unit functions only active on TC connection
C = Unit functions only active on RTD 2 wire connection
6.2.4 Configuration using HART
®
protocol and PC configuration soft-
ware ReadWin
®
2000
The configuration of the transmitter can be done using both the HART
®
protocol and the Read-
Win
®
2000 configuration software. The following table shows the structure of the interactive menu
led operation of READWIN
®
2000.
Configurable parameters (Unit function description see “Description of unit functions” on page 20)
Standard settings Type of sensor
Connection mode (2-,3-, or 4-wire connection on RTD)
Units (°C, °F or K)
Measurement range start value
Measurement range end value
Coefficient X0 to X4 (on sensor type polynom RTD/TC)
Temp.-compensation (on sensor type polynom TC)
Expanded settings Cold junction compensation internal/external (on TC)
Temperature external (on TC with cold junction compensation external)
Cable resistance compensation (on RTD 2-wire connection)
Fault condition reaction
Output (4 to 20 mA/20 to 4 mA)
Damping (filter)
–Offset
TAG (Measurement point description)
Identifier (Descriptor)
Service functions Simulation (on/off)
Reset/factory default
Series number (only display)
Operation code (=release code 281)