TMT182 7 Maintenance
Endress+Hauser 25
7Maintenance
Maintenance The temperature head transmitter has no moving parts and requires minimal scheduled mainte-
nance.
Sensor Checkout
To determine whether the sensor is at fault, replace it with another sensor or connect a test sensor
locally at the transmitter to test remote sensor wiring. Select any standard, off-the-shelf sensor for
use with a TMT182 temperature transmitter, or consult the factory for a replacement special sensor
or transmitter combination.
8 Accessories
Accessories Commubox FXA191, PC-Software Commuwin II and ReadWin
®
2000, DIN rail clip according to
IEC 60715 for E+H temperature head transmitters (order code: 51000856), Field housing TAF10
suitable for all E+H temperature head transmitters.
ReadWin
®
2000 can be downloaded free of charge from the internet from the following address:
www.readwin2000.com
Please contact your supplier when ordering (e.g. spare parts)!
When ordering accessories or spare parts, please state the serial number of the unit!
9 Trouble-shooting
9.1 Trouble-shooting instructions
If faults occur after commissioning or during measurement, always start any trouble-shooting
sequence using the following check. The user is led towards the possible fault cause and its rectifi-
cation via question and answer.
9.2 Application fault messages
Application fault
messages
Application fault messages are shown in the display of the HART
®
hand operating module
"DXR275, DXR375" once the menu point "ERROR CODE" has been selected or in the PC operating
surface of Commuwin II (V9H0 - ERROR CODE).
Fault code Cause Action/cure
0 No fault, Warning None
10 Hardware fault (unit defective) Replace head transmitter
11 Sensor short circuit Check sensor
12 Sensor cable open circuit Check sensor
13 Reference measurement point defec-
tive
None
14 Unit not calibrated Return head transmitter to
manufacturer