Use in safety instrumented systems Temperature transmitter iTEMP TMT82
18 Endress+Hauser
NOTICE
The configuration of the parameters for a SIL device must be documented!
Enter the configured parameters in the 'Set value' column. The date, time and the SIL
checksum that is subsequently displayed must be documented.
All the safety-related parameters (SRP) and their settings can be saved locally and
printed out using the "Save results as PDF" button. →  2,  20
The 'Commissioning or proof testing report' is suitable for this purpose →  35
The SIL checksum can be used to verify the configured parameters of several devices.
5.2.2 Locking in the expert mode, SIL mode activation = SiMA
The user interface can differ from the screens shown here depending on the operating tool
used and the selected language.
NOTICE
Interruption to SIL mode activation
In the course of the SIL mode activation process in the expert mode, the transmitter
outputs a failure current ≥ 21.5 mA(High alarm). If an error occurs during SIL mode
activation in the expert mode or if the process is interrupted, SIL mode activation is not
completed successfully and must be performed again.
SIL mode activation process
1.
A0053701
If the transmitter is not in the original as-delivered state, proceed as follows:
In the menu Setup → Extended setup → Administration, select 'To delivery settings' in
the Reset device option.
2. Press ENTER to confirm.
3. Configure all parameters as required for use in the safety instrumented system.