Appendix Temperature transmitter iTEMP TMT82
38 Endress+Hauser
7.2.1 Parameter settings for the SIL mode
Parameter name Default setting Set value Checked
Enter access code 0
Lower measuring range (4 mA) 0
Upper measuring range (20 mA) 100
Failure current 22.5 mA
Failure mode High alarm
Out of range category Factory setting:
Maintenance required
(M)
Sensor type 1 Pt100 IEC60751
Sensor type 2 No sensor
Upper sensor limit 1
1)
+850 °C
Lower sensor limit 1
1)
–200 °C
Upper sensor limit 2
1)
-
Lower sensor limit 2
1)
-
Sensor offset 1 0
Sensor offset 2 0
Connection type 1 4-wire (RTD)
Connection type 2 2-wire (TC)
Reference junction 1,2 Internal measurement
(TC)
RJ preset value 1,2 0 (for
Preset value setting)
Call.-V. Dusen coeff. A, B and C
sensor 1
1)
A: 3.910000e-003
B: -5.780000e-007
C: -4.180000e-012
Call.-V. Dusen coeff. A, B and C
sensor 2
1)
A: 3.910000e-003
B: -5.780000e-007
C: -4.180000e-012
Call.-V. Dusen coeff. R0 sensor
1
1)
100 Ω
Call.-V. Dusen coeff. R0 sensor
2
1)
100 Ω
Polynomial coeff. A, B sensor 1
1)
A = 5.49630e-003
B = 6.75560e-006
Polynomial coeff. A, B sensor 2
1)
A = 5.49630e-003
B = 6.75560e-006
Polynomial coeff. R0 sensor 1
1)
100 Ω
Polynomial coeff. R0 sensor 2
1)
100 Ω
Unit °C
Mains frequency filter 50 Hz
Drift/difference mode Disable
Drift/difference alarm category Maintenance required
(M)
Drift/difference alarm delay 0 s
Drift/difference set point 999
Device temperature alarm Out of specification (S)