iTEMP TMT82 Mounting
Endress+Hauser 15
4.2.2 Mounting the DIN rail transmitter
NOTICE
Wrong orientation
Measurement deviates from the maximum accuracy rating when a thermocouple is connected
and the internal reference junction is used.
Mount the device vertically and ensure it is oriented correctly (sensor connection at
bottom / power supply at top)!
1.
2.
3.
1.
3.
A0017821
 8 Mounting the DIN rail transmitter
1. Slide the upper DIN rail clip upwards and the lower clip downwards until they click into
place.
2. Fit the device on the DIN rail from the front.
3. Slide the two DIN rail clips back together until they click into place.
4.3 Post-mounting check
After mounting the device, always run the following final checks:
Device condition and specifications Notes
Is the device undamaged (visual inspection)? -
Do the ambient conditions match the device specification (e.g. ambient temperature,
measuring range, etc.)?
→  10