Electrical connection iTEMP TMT82
24 Endress+Hauser
A0024523
15 Connection tips to retain IP67 protection
5.7 Post-connection check
Device condition and specifications Notes
Is the device or cable undamaged (visual check)? --
Electrical connection Notes
Does the supply voltage match the information on the
nameplate?
• Head transmitter: U = 11 to 42 V
DC
• DIN rail transmitter: U = 12 to 42 V
DC
• SIL mode: U = 11 to 32 V
DC
for the head transmitter or
U = 12 to 32 V
DC
for the DIN rail transmitter
• Other values apply in the hazardous area, see the
corresponding Ex Safety Instructions (XA).
Are the mounted cables relieved of tension? --
Are the power supply and signal cables connected
correctly?
→ 17
Are all the screw terminals well tightened and have the
connections of the push-in terminals been checked?
--
Are all the cable entries installed, tightened and sealed? --
Are all housing covers installed and firmly tightened? --