iTEMP TMT82 Mounting
Endress+Hauser 9
3.5 Certificates and approvals
The device left the factory in a safe operating condition. The device complies with the
requirements of the standards EN 61010-1 "Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use" and with the EMC requirements as per the
IEC/EN 61326 series.
3.5.1 CE/EAC mark, Declaration of Conformity
The device meets the legal requirements of the EU/EEU guidelines. The manufacturer
confirms that the device is compliant with the relevant guidelines by applying the CE/EAC
mark.
3.5.2 HART
®
protocol certification
The temperature transmitter is registered by the HART
®
FieldComm Group. The device meets
the requirements of the HART
®
Communication Protocol Specifications, Revision 7 (HCF 7.6).
3.5.3 Functional safety
The two device versions (head transmitter/DIN rail device) are optionally available for use in
safety systems as per IEC 61508.
• SIL 2: Hardware version
• SIL 3: Software version
4 Mounting
4.1 Mounting requirements
4.1.1 Mounting location
• Head transmitter:
• In the terminal head, flat face, as per DIN EN 50446, direct mounting on insert with cable
entry (middle hole 7 mm)
• In the field housing, separated from the process
• In the field mount housing with separate terminal compartment, if stable sensors are
used, the device can be fitted directly on the assembly, otherwise it has to be mounted
separated from the process
• With clip on DIN rail as per IEC 60715, TH35
• DIN rail transmitter:
In DIN rail housing on DIN rail as per IEC 60715, TH35