iTEMP TMT82 Commissioning
Endress+Hauser 27
6.2 Configuration of transmitter and HART
®
protocol
The transmitter and measured value display are configured via the HART
®
protocol or CDI (=
Endress+Hauser Common Data Interface). The following operating tools are available for this
purpose:
Operating tools
FieldCare, Field Xpert
(Endress+Hauser)
SIMATIC PDM
(Siemens)
AMS Device Manager
(Emerson Process Management)
Field Communicator 375, 475
(Emerson Process Management)
NOTICE
The following applies if using the device in hazardous areas: Before accessing the device
with the Commubox FXA291 via the CDI (= Endress+Hauser Common Data Interface),
disconnect the transmitter from the power supply, terminals (1+) and (2-).
Failure to comply with this instruction can result in damage to parts of the electronics.
The configuration of device-specific parameters is described in detail in the Operating
Instructions for the device.
7 Commissioning
Switching on the transmitter
Once the final checks have been successfully completed, it is time to switch on the supply
voltage. The transmitter performs a number of internal test functions after power-up. During
this process, a sequence containing device information appears on the display. The device is
operational after approx. 30 seconds, and the plug-in display after approx. 33 seconds in
normal operating mode! Normal measuring mode commences as soon as the switch-on
procedure is completed. Measured values and status values appear on the display.