Levelflex FMP56, FMP57
10 Endress+Hauser
Signal on alarm
Maintenance information can be viewed via the following interfaces:
• Local display:
– Error symbol (in accordance with NAMUR Recommendation NE 107)
– Plain text display
• Current output: failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):
– Minimum alarm: 3.6 mA
– Maximum alarm (= factory setting): 22 mA
• Digital interface such as HART communication or CDI service interface (in accordance with NAMUR
Recommendation NE 107)
Linearization
The linearization function of the Micropilot M allows the conversion of the measured value into any unit of
length or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-programmed.
Other tables of up to 32 value pairs can be entered manually or semi-automatically.
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data HART
Manufacturer ID
17 (0x11)
Device type ID 0x34
HART specification 6.0
Device description files (DTM,
DD)
Information and files under:
• www.endress.com
• www.hartcom.org
HART load
Min. 250 W
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Calculated DC
Supported functions
• Burst mode
• Additional transmitter status
PROFIBUS PA
Manufacturer ID
17 (0x11)
Ident number 0x1558
Profile version 3.02
GSD file Information and files under:
• www.endress.com
• www.profibus.org
GSD file version