Levelflex FMP56, FMP57
Endress+Hauser 15
A0013759
1 Terminals switching output
2 Cable entry
Switching output
Function Open collector switching output
Switching behavior Binary (conductive or non-conductive), switches when the programmable switch point is
reached
Failure mode non-conductive
Eectrical connection values U = 10.4 to 35 V
DC
, I = 0 to 70 mA
Insulation voltage floating, Insulation voltage 1 350 V
DC
to power supply aund 500 V
AC
to ground
Switch point freely programmable, separately for switch-on and switch-off point
Switching delay freely programmable from 0 to 100 sec. , separately for switch-on and switch-off point
Number of switching cycles corresponds to the measuring cycle
Signal source
device variables
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
Number of switching cycles unlimited
Supply voltage
An external power supply is required.
Various supply units can be ordered from Endress+Hauser: see "Accessories" section (® ä 50)
2-wire, 4-20mA HART, passive
"Power Supply, Output"
1)
Outputs Terminal voltage "Approval"
2)
A: 2-wire; 4-20mA HART 1 11.5 to 35 V Non-Ex, Ex nA, CSA GP
11.5 to 32 V Ex ic
11.5 to 30 V Ex ia / IS
13.5 to 30 V Ex d / XP, Ex ic(ia), Ex tD / DIP
C: 2-wire; 4-20mA HART, 4-20mA 1 13.5 to 30 V all
2 12 to 30 V all
1) Feature 020 of the product structure
2) Feature 010 of the product structure
Load (® ä 17)