Levelflex FMP56, FMP57
Endress+Hauser 13
2-wire, 4-20 mA HART, 4...20mA
Without integrated overvoltage protection
4
+
1
2
+
3
+
2
3
10
6
4
8
5
4...20mA
+
+
4...20mA
+
1
77
9
11
12
A0013923
1
Cable entry for current output 1
2 Terminal for current output 1
3
Supply voltage for current output 1 (e.g. RN221N); Observe terminal voltage (® ä 16)
4
HART communication resistor (³ 250 W): Observe maximum load (® ä 17)
5 Connection for Field Communicator 375/475 or Commubox FXA195
6
Analog display device ; observe maximum load (® ä 17)
7
Observe cable specification (® ä 16)
8 Cable entry for current output 2
9 Terminal for current output 2
10
Supply voltage for current output 2 (e.g. RN221N); Obesrve terminal voltage (® ä 16)
11 Analog display device ; observe maximum load
12 Terminal for the potential equalization line
This version is also suited for single-channel operation. In this case, current output 1 must be used.