Levelflex FMP56, FMP57
24 Endress+Hauser
A0014199
1 Lower edge of the nozzle
2
Approx. flush with the lower edge of the nozzle (± 50 mm/2")
3 Plate
4
Pipe Æ 150 to 180 mm (6 to 7 inch)
Nozzle diameter Plate diameter
300 mm (12") 280 mm (11")
³ 400 mm (16") ³ 350 mm (14")
Installation in concrete silos
Installation, for example, into a thick concrete ceiling should be made flush with the lower edge. Alternatively,
the probe can also be installed into a pipe that must not protrude over the lower edge of the silo ceiling. The
pipe should kept at a minimum length. Installation suggestions see diagram.
≥
≥
100
4
≥
≥
100
4
mm(in)
ø80...150
(ø3.2...6)
1
3
2
A0014138
1
Metal sheet
2 Metal tube
3 Extension rod / Centering HMP40 (see "Accessories")
Note for installations with rod extension/center washer (accesories): Strong dust generation can lead to build-
up behind the center washer. This can cause an interference signal. For other installation possibilities please
contact Endress+Hauser.