Commissioning Liquicap M FTI51, FTI52
72 Endress+Hauser
6.3 Commissioning with electronic inserts
FEI53 or FEI57S
This chapter describes the process for commissioning the device with electronic insert versions
FEI53 and FEI57S.
!
Note!
The measuring system is not operational until you have carried out a calibration at the switching
unit.
For information on how to carry out the calibration, refer to the documentation for the Nivotester
switching device FTCxxx.
6.3.1 Setting the alarm response if the measuring range is exceeded
BA300Fen016
!
Note!
• With this setting, you can determine the alarm response of the measuring system If the measuring
range is exceeded. You can switch the alarm on or off If the measuring range is exceeded.
• All other settings with regard to the alarm response have to be configured on the respective
Nivotester switching device.
A
-
+
FEI5x
FEI5x
0.....500pFStandard
0...1600pF
B
1
2
LED
on
flashing
of
f
DIP switch Function Light emitting diodes (LED signals)
1 (green)
Operational
2 (red)*/**
Fault
A
Standard: If the measuring range is exceeded no alarm is output (factory
setting).
Flashes*** Off
A
: If the measuring range is exceeded an alarm is output. Flashes*** Off
* The red LED flashes if there is a fault that you can correct.
** The red LED lights up continuously if the device has a fault that cannot be corrected. See also Page 78,
"Troubleshooting".
*** Flashes at 5-second intervals.