Liquicap M FTI51, FTI52 Installation
Endress+Hauser 35
3.5 With separate housing
!
Note!
The maximum connection length between the probe and the separate housing is 6 m (L4). The desired
length must be quoted when ordering a Liquicap M with a separate housing.
The total length L = L1 + L4 should not exceed 10 m (e.g. for rope probes).
If the connecting cable is to be shortened or passed through a wall, it must be separated from the process
connection. See "Documentation" => "Operating Instructions" on
Page 88.
L00-FMI5xxxx-14-00-06-xx-003
Rod length L1 max. 4 m
Rope length L1 max. 9.7 m (the maximum total length of L1 + L4 should not exceed 10 m.)
Extension heights
!
Note!
The cable has a bending radius of r 100 mm which may not be undershot!
E
E
X
X
Zone 1
Zone 1
L4
L4
6m
6 m
£
£
E
E
X
X
Zone 0
Zone 0
L1
L1
Housing side: wall mounting Housing side: pipe mounting Sensor side
L00-FMI5xxxx-06-05-xx-xx-049
~61 mm
~75 mm
~41 mm
~41 mm
B
B
H1
H1
H4
D
r 100 mm³
r 100 mm³