Operation options Liquiphant FTL62
32 Endress+Hauser
1
2
3
!
"d
3.5
24/25 mm
8.0 Nm
A0018023
 26 Example of coupling with cable entry, electronic insert with terminals
1 M20 coupling (with cable entry), example
2
Conductor cross-section maximum 2.5 mm
2
(AWG14), ground terminal on inside in housing +
terminals on the electronics
3
Conductor cross-section maximum 4.0 mm
2
(AWG12), ground terminal on outside of the housing
(example: plastic housing with outer protective ground connection (PE))
⌀d Nickel-plated brass 7 to 10.5 mm (0.28 to 0.41 in),
Plastic 5 to 10 mm (0.2 to 0.38 in),
Stainless steel 7 to 12 mm (0.28 to 0.47 in)
Pay attention to the following when using the M20 coupling
Following cable entry:
Counter-tighten the coupling
Tighten the union nut of the coupling with 8 Nm (5.9 lbf ft)
Screw the enclosed coupling into the housing with 3.75 Nm (2.76 lbf ft)
7 Operation options
7.1 Operating concept
Operation with button and DIP switches on the electronic insert
Display with optional Bluetooth module and SmartBlue app via Bluetooth® wireless
technology, see the Operating Instructions
Indication of operational status (switch status or alarm status) with optional LED module
(signal lights visible from the outside), see the Operating Instructions