Micropilot FMR20 HART
8 Endress+Hauser
The range under reference conditions is 25 m (82 ft)
Incorrect operation by unauthorized persons is prevented by means of encrypted communication
and password encryption
The Bluetooth® wireless technology interface can be deactivated
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
Alarm current: 22.5 mA (in accordance with NAMUR recommendation NE 43)
Operating tool via digital communication (HART) or SmartBlue (app)
Status signal (as per NAMUR Recommendation NE 107)
Plain text display with remedial action
Linearization
The linearization function of the device allows the conversion of the measured value into any unit of
length, weight, flow or volume. In DeviceCare and FieldCare, there are preprogrammed linearization
tables for volume calculation in vessels.
Pre-programmed linearization curves
Horizontal cylindrical tank
Sphere
Tank with pyramid bottom
Tank with conical bottom
Tank with flat bottom
Other linearization tables of up to 32 value pairs can be entered manually.
Protocol-specific data, HART
Manufacturer ID
17 (0x11)
Device type ID
44 (0x112c)
HART specification
7.0
Device description files (DTM)
Information and files under:
www.endress.com
www.hartcomm.org
HART load
Min. 250 Ω
HART device variables
Assignment of HART device variables is fixed and cannot be changed.
Measured values for PV (primary variable)
Level linearized
Advanced diag. measured values for SV (secondary variable)
Distance
Advanced diag. measured values for TV (tertiary variable)
Relative echo amplitude
Advanced diag. measured values for QV (quarternary variable)
Temperature
Supported functions
Additional transmitter status
Multidrop current
4 mA
Time for connection setup
< 1 s