EasyManua.ls Logo

Endress+Hauser Micropilot FMR67 - Safety Instructions: Installation; Safety Instructions: Special Conditions

Endress+Hauser Micropilot FMR67
44 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Micropilot FMR67 XA01554F-A
Endress+Hauser 17
Avoid electrostatic charging:
Of plastic surfaces (e.g. housing, sensor element, special varnishing, attached additional
plates, ..)
Of isolated capacities (e.g. isolated metallic plates)
Modifications to the device can affect the explosion protection and must be carried out by staff
authorized to perform such work by Endress+Hauser.
Refer to the temperature tables for the relationship between the permitted ambient temperature
for the sensor and/or transmitter, depending on the range of application and the temperature
class.
Safety instructions:
Special conditions
Permitted ambient temperature range at the electronics housing:
–40 °C ≤ T
a
≤ +80 °C
Observe the information in the temperature tables.
In the case of process connections made of polymeric material or with polymeric coatings, avoid
electrostatic charging of the plastic surfaces.
In the event of additional or alternative special varnishing on the housing or other metal parts:
Observe the danger of electrostatic charging and discharge.
Do not rub surfaces with a dry cloth.
Avoid electrostatic charging of the sensor (e.g. do not rub dry and install outside the filling flow).
Device type FMR67 and Basic specification, Position 11-13 (Process Connection) = XxA
Changing the position of the alignment device must be impossible:
After the alignment of the antenna via the pivot bracket
After tightening of the clamping flange
After setting the damping ring (torque 15 Nm)
Degree of protection IP67 must be fulfilled.
Device type FMR67 and Basic specification, Position 14 (Air Purge Connection) = 1, 2
If equipment with Ga/Gb or Da/Db is required: In the closed state the minimum degree of
protection of the installation must be IP67.
After removing the air purge connection: Lock the opening with a suitable plug.
Torque: 6-7 Nm
For Da/Db: thread engagement > 5 turns
Degree of protection IP67 must be fulfilled.
Safety instructions:
Installation
A
2
1
1
5
4
6
3
A0031947
2
A Zone 20, Zone 21
1 Potential equalization line
2 Electronics compartment Ex ia; Electronic insert
3 Power supply
4 Connection compartment Ex tb
5 Tank; Zone 20, Zone 21
6 Potential equalization

Other manuals for Endress+Hauser Micropilot FMR67

Related product manuals