Micropilot FMR67B PROFINET with Ethernet-APL Diagnostics and troubleshooting
Endress+Hauser 57
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
168 Build-up detected Check process conditions M Warning
1)
Diagnostic of electronic
232 Real time clock
defective
Replace main electronics M Warning
242 Firmware incompatible 1. Check software
2. Flash or change main electronic
module
F Alarm
252 Module incompatible 1. Check if correct electronic
module is plugged
2. Replace electronic module
F Alarm
270 Main electronics
defective
Replace main electronics F Alarm
272 Main electronics faulty 1. Restart device
2. Contact service
F Alarm
273 Main electronics
defective
Replace main electronics F Alarm
282 Data storage
inconsistent
Restart device F Alarm
283 Memory content
inconsistent
1. Restart device
2. Contact service
F Alarm
287 Memory content
inconsistent
1. Restart device
2. Contact service
M Warning
331 Firmware update failed 1. Update firmware of device
2. Restart device
M Warning
388 Electronics and
HistoROM defective
1. Restart device
2. Replace electronics and
HistoROM
3. Contact service
F Alarm
Diagnostic of configuration
410 Data transfer failed 1. Retry data transfer
2. Check connection
F Alarm
412 Processing download Download active, please wait C Warning
435 Linearization faulty Check linearization table F Alarm
436 Date/time incorrect Check date and time settings. M Warning
1)
437 Configuration
incompatible
1. Update firmware
2. Execute factory reset
F Alarm
438 Dataset different 1. Check dataset file
2. Check device parameterization
3. Download new device
parameterization
M Warning
484 Failure mode
simulation active
Deactivate simulation C Alarm
485 Process variable
simulation active
Deactivate simulation C Warning
495 Diagnostic event
simulation active
Deactivate simulation S Warning
538 Configuration Sensor
Unit invalid
1. Check sensor configuration
2. Check device configuration
F Alarm
585 Simulation distance Deactivate simulation C Warning