Tankside Monitor NRF81 Operating menu
Endress+Hauser 133
Selection Cu50 (w=1.428, GOST)
Cu53 (w=1.426, GOST)
Cu90@0°C (w=1.4274, GOST)
Cu100@25°C (w=1.4274, GOST)
Cu100@0°C(w=1.4274, GOST)
Pt46 (w=1.391, GOST)
Pt50 (w=1.391, GOST)
Pt100(385) (a=0.00385, IEC751)
Pt100(389) (a=0.00389, Canadian)
Pt100(391) (a=0.003916, JIS1604)
Pt100 (w=1.391, GOST)
Pt500(385) (a=0.00385, IEC751)
Pt1000(385) (a=0.00385, IEC751)
Ni100(617) (a=0.00617, DIN43760)
Ni120(672) (a=0.00672, DIN43760)
Ni1000(617) (a=0.00617, DIN43760)
Factory setting Pt100(385) (a=0.00385, IEC751)
Additional information
Read access Operator
Write access Maintenance
RTD connection type
Navigation  Setup → Advanced setup → Input/output → Analog IP → RTD connection type
Prerequisite Operating mode (→  132) = RTD temperature input
Description Defines the connection type of the RTD.
Selection 4 wire RTD connection
2 wire RTD connection
3 wire RTD connection
Factory setting 4 wire RTD connection
Additional information
Read access Operator
Write access Maintenance
Process value
Navigation  Setup → Advanced setup → Input/output → Analog IP → Process value
Prerequisite Operating mode (→  132)Disabled
Description Shows the measured value received via the analog input.