Operating menu Tankside Monitor NRF81
136 Endress+Hauser
User entry –213 to 927 °C
Factory setting 250 °C
Additional information
Read access Operator
Write access Maintenance
Probe position
Navigation Setup → Advanced setup → Input/output → Analog IP → Probe position
Prerequisite Operating mode (→ 132) = RTD temperature input
Description Position of the temperature probe, measured from zero position (tank bottom or datum
plate). This parameter, in conjunction with the measured level, determines whether the
temperature probe is still covered by the product. If this is no longer the case, the status of
the temperature value will be 'invalid'.
User entry –5 000 to 30 000 mm
Factory setting 5 000 mm
Additional information
Read access Operator
Write access Maintenance
Damping factor
Navigation Setup → Advanced setup → Input/output → Analog IP → Damping factor
Prerequisite Operating mode (→ 132) ≠ Disabled
Description Defines the damping constant (in seconds).
User entry 0 to 999.9 s
Factory setting 0 s
Additional information
Read access Operator
Write access Maintenance