Operating menu Tankside Monitor NRF81
146 Endress+Hauser
Input value percent
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Input value percent
Prerequisite Operating mode (→  138) = 4..20mA input or HART master+4..20mA input
Description Shows the input value as a percentage of the complete 4...20mA current range.
Additional information
Read access Operator
Write access -
Damping factor
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Damping factor
Prerequisite Operating mode (→  138)Disabled or HART master
Description Defines the damping constant (in seconds).
User entry 0 to 999.9 s
Factory setting 0 s
Additional information
Read access Operator
Write access Maintenance
Used for SIL/WHG
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Used for SIL/WHG
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
The device has a SIL approval.
Description Determines whether the discrete I/O module is in SIL/WHG mode.
Selection Enabled
Disabled
Factory setting Disabled
Additional information
Read access Operator
Write access Maintenance