Tankside Monitor NRF81 Operating menu
Endress+Hauser 177
Air temperature
Navigation Setup → Advanced setup → Application → Tank configuration → Temperature → Air
temperature
Description Shows the air temperature.
Additional information
Read access Operator
Write access -
Vapor temp source
Navigation Setup → Advanced setup → Application → Tank configuration → Temperature
→ Vapor temp source
Description Defines the source from which the vapor temperature is obtained.
Selection • Manual value
• HART device 1 ... 15 vapor temp
• AIO B1-3 value
• AIO C1-3 value
• AIP B4-8 value
• AIP C4-8 value
Factory setting Manual value
Additional information
Read access Operator
Write access Maintenance
Manual vapor temperature
Navigation Setup → Advanced setup → Application → Tank configuration → Temperature
→ Manual vapor temperature
Prerequisite Vapor temp source (→ 177) = Manual value
Description Defines the manual value of the vapor temperature.
User entry –50 to 300 °C
Factory setting 25 °C
Additional information
Read access Operator
Write access Maintenance