Operating menu Tankside Monitor NRF81
176 Endress+Hauser
Liquid temperature
Navigation Setup → Advanced setup → Application → Tank configuration → Temperature
→ Liquid temperature
Description Shows the average or spot temperature of the measured liquid.
Additional information
Read access Operator
Write access -
Air temperature source
Navigation Setup → Advanced setup → Application → Tank configuration → Temperature → Air
temperature source
Description Defines source from which the air temperature is obtained.
Selection • Manual value
• HART device 1 ... 15 temperature
• AIO B1-3 value
• AIO C1-3 value
• AIP B4-8 value
• AIP C4-8 value
Factory setting Manual value
Additional information
Read access Operator
Write access Maintenance
Manual air temperature
Navigation Setup → Advanced setup → Application → Tank configuration → Temperature
→ Manual air temperature
Prerequisite Air temperature source (→ 176) = Manual value
Description Defines the manual value of the air temperature.
User entry –50 to 300 °C
Factory setting 25 °C
Additional information
Read access Operator
Write access Maintenance