EasyManua.ls Logo

Endress+Hauser NRF81 - Page 182

Endress+Hauser NRF81
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating menu Tankside Monitor NRF81
182 Endress+Hauser
Factory setting 0 bar
Additional information
Read access Operator
Write access Maintenance
P1 position
Navigation  Setup → Advanced setup → Application → Tank configuration → Pressure → P1
position
Description Defines the position of the bottom pressure transmitter (P1), measured from zero position
(tank bottom or datum plate).
User entry –10 000 to 100 000 mm
Factory setting 5 000 mm
Additional information
Read access Operator
Write access Maintenance
P1 offset
Navigation  Setup → Advanced setup → Application → Tank configuration → Pressure → P1
offset
Description Offset for the bottom pressure (P1). The offset is added to the measured pressure prior to
any tank calculation.
User entry –25 to 25 bar
Factory setting 0 bar
Additional information
Read access Operator
Write access Maintenance
P1 absolute / gauge
Navigation  Setup → Advanced setup → Application → Tank configuration → Pressure → P1
absolute / gauge
Description Defines whether the connected pressure transmitter measures an absolute or a gauge
pressure.
Selection Absolute
Gauge