Tankside Monitor NRF81 Operating menu
Endress+Hauser 207
Manual density
Navigation  Setup → Advanced setup → Application → Tank calculation → HTG → Manual
density
Description Defines the manual density.
User entry 0 to 3 000 kg/m³
Factory setting 800 kg/m³
Additional information
Read access Maintenance
Write access Maintenance
Minimum level
Navigation  Setup → Advanced setup → Application → Tank calculation → HTG → Minimum level
Description Defines the minimum level below which no HTG calculation will take place.
User entry 0 to 20 000 mm
Factory setting 7 000 mm
Additional information
Read access Operator
Write access Maintenance
Minimum pressure
Navigation  Setup → Advanced setup → Application → Tank calculation → HTG → Minimum
pressure
Description Defines the minimum pressure below which no HTG calculation takes place.
User entry 0 to 100 bar
Factory setting 0.1 bar
Additional information
Read access Operator
Write access Maintenance