Operating menu Tankside Monitor NRF81
216 Endress+Hauser
A
B
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
10
A0029539
 57 Principle of the limit evaluation
A Alarm mode (→  215) = On
B Alarm mode (→  215) = Latching
1 HH alarm value (→  218)
2 H alarm value (→  218)
3 L alarm value (→  219)
4 LL alarm value (→  219)
5 HH alarm (→  219)
6 H alarm (→  220)
7 L alarm (→  220)
8 LL alarm (→  220)
9 "Clear alarm (→  221)" = "Yes" or power off-on
10 Hysteresis (→  222)
Error value
Navigation  Setup → Advanced setup → Application → Alarm → Alarm → Error value
Prerequisite Alarm mode (→  215)Off
Description Defines the alarm to be issued if the input value is invalid.
Selection No alarm
HH+H alarm
H alarm
L alarm
LL+L alarm
All alarms
Factory setting All alarms
Additional information
Read access Operator
Write access Maintenance