Proservo NMS80 Electrical connection
Endress+Hauser 37
6.1.7 Connection of the "Analog I/O" module for active usage
In the active usage the supply voltage for the communication line is supplied by the
device itself. There is no need of an external power supply.
The wiring must be in accordance with the intended operating mode of the Analog I/O
module; see the drawings below.
Maximum current consumption of the connected HART devices: 24 mA
(i.e. 4 mA per device if 6 devices are connected).
Output voltage of the Ex-d module: 17.0 V@4 mA to 10.5 V@22 mA
Output voltage of the Ex-ia module: 18.5 V@4 mA to 12.5 V@22 mA
"Operating mode" = "4..20mA output" or "HART slave +4..20mA output"
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
2
2
3
3
4
4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
i
G
1
3
2
POWER
-
+
E
G
F
1
1 3
2
2 4
HR
CDI
on
i
C
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
G
1
3
2
b
a
A0027932
 15 Active usage of the Analog I/O module in the output mode
a HART signal output
b Analog signal evaluation

Other manuals for Endress+Hauser Proservo NMS80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Proservo NMS80 and is the answer not in the manual?

Endress+Hauser Proservo NMS80 Specifications

General IconGeneral
BrandEndress+Hauser
ModelProservo NMS80
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals