RIA45 Wiring
Endress+Hauser 9
4.4 Post-installation check
Is the seal undamaged?
Is the mounting frame securely fastened on the housing of the device?
Are the threaded rods properly tightened?
Is the device located in the center of the panel cutout?
Is the spacer mounted (Ex option)?
5 Wiring
L
WARNING
Danger! Electric voltage!
The entire connection of the device must take place while the device is de-energized.
The protective ground connection must be established before all other connections. If the
protective ground is disconnected, this can be a source of danger.
Before commissioning the device, make sure that the supply voltage matches the voltage
specifications on the nameplate.
Provide suitable switch or circuit breaker in building installation. This switch must be
provided close to the device (within easy reach) and marked as a circuit breaker.
An overcurrent protection element (rated current ≤ 10 A) is required for the power cable.
Observe the terminal designation on the front of the device.
The mixed connection of safety extra-low voltage and dangerous contact voltage to the
relay is permitted.
5.1 Electrical connection
A loop power supply (LPS) is provided for every input. The loop power supply is primarily
designed to supply power to 2-wire sensors and is galvanically isolated from the system and
the outputs.