EasyManua.ls Logo

Endress+Hauser Soliswitch FTE20 - Installation Conditions

Endress+Hauser Soliswitch FTE20
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting Soliswitch FTE20
8 Endress+Hauser
4.1.2 Transport and storage
Please note the following:
Pack the device so that is protected against impact for storage and transport. The original
packaging offers the best protection for this.
The permitted storage temperature is –20 to 60 °C (–4 to 140 °F).
4.2 Installation conditions
Correct and incorrect installation positions are indicated in →  2,  8.
The device must be protected against direct sunshine. A weather protection cover is available
as an accessory, see the "Accessories" section →  30.
The dimensions of the device are provided in the "Technical data" section →  16,  27.
A0021567
 2 Orientations of the point level switch, dimensions in mm (in)
Permitted orientations Forbidden orientations
1: Vertical from the top 6: In direction of solids flow
2: Angled from the top 7: Installation coupling too long
3: From the side 8: Horizontal with shaft length >300 mm (11.8 in)
4: From the side with protective cover against falling
solids
5: From the bottom (device must be protected
against shock-type loads)
Ambient temperature range
–20 to 60 °C (–4 to 140 °F)
Medium temperature range
–20 to 80 °C (–4 to 176 °F)

Related product manuals