Envoy Installation and Operation
2014 Enphase Energy Inc. 141-00011 Rev 05
55
Message Shown on
Events and Inventory
Screens
Description
Bad Flash Image
Recommended Action: Contact Enphase Energy customer support.
Description: The microinverter is not producing power due to a software problem.
Commanded Reset
Recommended Action: No action is required; it will automatically resume normal
operation momentarily.
Description: The microinverter was reset, either following a successful software
download or by user command.
Control Request
Recommended Action: No action is required.
Description: The Envoy has received a control request made via the Envoy
interface (Administration > Device Conditions and Controls page) or via Enlighten.
This uncommon condition will occur only during isolated troubleshooting
procedures by Enphase personnel.
Critical Temperature
Recommended Action: This condition should correct itself. No action is required.
Description: This rare condition occurs if the microinverter reports an internal
temperature that exceeds its rated range. It reacts by producing less power to
reduce internal temperature. This reflects internal temperature coming from a
sensor inside the microinverter, not the ambient temperature. Once the internal
temperature of the microinverter is once again within normal limits, it will resume
full power production and this event message will clear.
If the condition persists: Contact your installer or Enphase Energy customer
support at support@enphase.com.
DC Power Too Low
Recommended Action: This condition should correct itself. No action is required.
Description: This condition may occur at sunrise or sunset, while the modules are
covered with snow, or during extreme weather. This event indicates that sunlight
levels are too low for effective production. Once sunlight levels increase, the
microinverter resumes power production and this event message will clear.
If the condition persists: Contact your installer or Enphase Energy customer
support at support@enphase.com.
DC Resistance Low -
Power Off
Recommended Action: To clear this error using the Envoy interface, follow the
directions on page 49. The insulation resistance (IR) sensor can be reset via the
Enphase Envoy's Device Conditions and Controls page, or Enlighten’s Current
Issues page. Note that the condition will not clear after sensor reset if the failure is
still present. If the condition persists, contact your installer or refer to the
Troubleshooting Guide at http://www.enphase.com/support.
Description: An IR sensor in the microinverter measures the resistance between
the positive and negative PV inputs to ground. If either resistance drops below a
threshold, the microinverter stops power production and raises this condition. This
may indicate defective module insulation, defective wiring or connectors, moisture
ingress, etc. Although the cause may be temporary, this microinverter condition
persists until the sensor is manually reset.
If the condition persists: If the event persists after clearing the condition from the
Envoy, contact your installer.
For further assistance, contact Enphase Energy customer support at
support@enphase.com.

Table of Contents

Other manuals for enphase Envoy

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the enphase Envoy and is the answer not in the manual?

enphase Envoy Specifications

General IconGeneral
ModelEnvoy
CategoryGateway
CompatibilityEnphase Microinverters
CommunicationWi-Fi, Ethernet
NetworkingIEEE 802.11 b/g/n
Operating Temperature-40°C to +65°C
Enclosure RatingIP30
Power Supply100-240 VAC
Power Consumption5W typical

Related product manuals